TH12
US style RTD sensor, cable probe

TH12
US style RTD sensor, cable probe ©Endress+Hauser

Cost efficient RTD sensor designed for use in the process industry or factory automation

The Pt100 cable probe is easy to install and provide a high operational safety due to reliable and accurate temperature measurement in common processes. Without additional thermowell the probe sheath is directly in contact with the process medium. This enables the cable probe to detect rapid temperature changes fast and accurate.

  • Avantages

    • High flexibility due to customized immersion length

    • Fast response time with reduced/tapered tip form

    • Simplified model structure: Competitively priced, offers great value. Easy to order and reorder

    • Improved galvanic isolation on most devices (2 kV)

  • Domaine d'application

    The TH12 temperature sensors are RTD's designed for use in the process industry or factory automation type of environment. They are made up of a measurement probe with a RTD, insulation and sheath.

    Among other applications the sensors can be used on:

    • ...

Caractéristiques et spécifications

Retour

Details

  • Principe de mesure

    Thermorésistance

  • Caractéristique / Application

    Style US

    Sonde à câble

    Raccord process sous forme de raccord ajustable

    Sans extension

  • Protecteur / tube de protection

    Sans (pas destiné à être utilisé avec un protecteur)

  • Insert / Sonde

    à isolation minérale (MI), flexible

    isolé PTFE, rigide

  • Diamètre extérieur tube de protection

    1/8'' (3,18 mm)

    3/16'' (4,76 mm)

    1/4'' (6,35 mm)

    3/8'' (9,53 mm)

  • Longueur dʹimmersion sur demande

    jusqu'à 4,877 mm (192,00'')

  • Matériau tube de protection/protecteur

    1.4401 (316)

  • Raccord process

    Raccord ajustable :

    NPT1/8"

    NPT1/4"

  • Forme de lʹextrémité

    Droite

    Réduite

  • Rugosité de surface Ra

    Non défini

  • Gamme de temperature de service

    PT 100 :

    -200 °C ...600 °C

    (-328 °F ... 1.112 °F)

  • Pression process max. (statique)

    à 20 °C : 40 bar (580 psi)

  • Précision

    Classe A selon IEC 60751

    Classe B selon IEC 60751

  • Temps de réponse

    63% rt = 2,0 s

  • Intégration transmetteur en tête

    oui (4 … 20 mA ; HART ; Profibus PA ; Foundation Fieldbus)

Documents / Manuels / Logiciels

Accessoires / pièces de rechange

Nr
Order code
Specification